Error Contents :
Transmission Error
Symptom :
Error Code display [ 1 4 ]
OPERATION LED is flashing.
Details :
Condition of occurrence :
When the signal is cut off for more than 10 minutes from the registered Indoor unit (not including Slave unit).
Release condition : 1. The signal has been received from the Indoor units that was creating the error.
2. MPU has been booted up. (Release from the reset operation, the power failure stand-by operation.
Trouble shooting 81
Cause 1 : Connection failure
Check transmission cable
Check disconnected power line for Indoor unit.
Check if convertor power line is disconnected.
OK
OK
Cause 3 : Remote Controller is defective.
Cause 1 : Remote Controller internal thermistor trouble
Replace Group Remote Controller.
Cause 2 : Check outside cause (Voltage drop or noise, etc.)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause
harmonic wave).
Thermostat Sensor display is flashing.
Cause 1 : Remote controller internal thermistor trouble
Replace remote controller.
Condition of occurrence : Thermistor in remote controller is open or shorted.
Release condition : Thermistor in remote controller is not open or shorted.
04-79
Trouble shooting 82
Error Contents :
Thermo Sensor Error
Symptom :
Details :
5. Wired Remote Controller (UTY-RNK )
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......