SERVICE PARTS INFORMATION 1
Compressor
Does not start up
Diagnosis method of Compressor (If Outdoor Unit 7 segment LED displays Error, refer to Trouble shooting )
Replace Compressor
Is any Indoor Unit in operation?
* If it is operated right after stopping
operation, 3 minutes start-up protection
by differential pressure is kicked on.
Stops soon after starting up
Abnormal noise
Check power supply voltage,open
fuse.
Is there open or loose connection
cable?
Check power supply voltage,open
fuse.
Is there open or loose connection
cable?
In case of constant speed compressor, check connection
and winding resistance.(Check if Protector is operated) Refer to
the next page.
In case of inverter compressor, check Filter PCB, Inverter
PCB, connection of Compressor, and winding resistance. (Refer
to the next page).
>> If there is no failure, the defect of Compressor can be
considered. (Compression part broken or valve defective.)
In case of constant speed
compressor, check connection and
winding resistance.(Check if Protector
is operated) Refer to the next page.
In case of inverter compressor, check
Filter PCB, Inverter PCB, connection of
Compressor, and winding resistance
(Refer to the next page).
>> If there is no failure, the defect of
Compressor is considered (Locked
compressor due to clogged dirt or
less oil)
Replace Compressor
Check if Refrigerant is leaking.
(Recharge Refrigerant)
Isn’t it Liquid Compression?
>> Check Low pressure value and if
it too high, check Indoor Unit.
(Indoor Unit EEV too much open, or
Indoor unit EEV that is not in
operation open.
Replace Compressor
Check power supply
voltage,open fuse. Is there
open or loose connection
cable?
Defective Compressor
can be considered.
(due to inside dirt clogging
or broken component)
Is Gas Pipe Valve open?
(Low Pressure is too low)
Check if Strainer is clogged.
MPa MPa
4-5 SERVICE PARTS INFORMATION
04-84
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......