Error Contents :
Power Supply Error
Symptom :
No display
Details :
Condition of occurrence : Normal power is not supplied. 7 segment indicator is defective.
Release condition : Normal power is supplied. 7 segment indicator is normal.
Cause 1 :
Power supply cable installation is defective or open.
Check following installation and reset the power supply.
(1) Installation of power cable on power supply terminal.
(2) Connection between Power PCB and Terminal.
(3) Connector condition between power PCB and Main PCB.
Error Contents :
Communication Error
Symptom :
Error code does not appear [ _ ]
Communication error occurs at connected equipment side.
Details :
Condition of occurrence : Network cable defective. External noise is applied.
Overlapping of Signal Amplifier address setting. System design mistake.
Release condition : Network cable
is connected. External noise is removed.
Overlapping of Signal Amplifier has been corrected. System design is normal.
OK
Cause 2 : External noise
OK
Cause 4 : System Design mistake
Check following items.(Refer to Installation Manual)
(1) Installation location of Terminal Resistor.
(Only 1 location on NS*)
(2) Cable length. (Within 500m maximum on NS*)
(3) Number of units connected
(Up to 64 units maximum on NS*)
(4) Communication cable specification.
(Use specified type.)
(5) Number of Signal Amplifier installed.
(Up to 8 units max. on system)
(6) Network cable shall not be connected in loop.
*NS : Network Segment
OK
Cause 1 :
Network cable installation is defective or open.
Check Network cable installation.
Cause 3 :
Overlapped address of Signal Amplifier.
Set up address again which does not overlap on system.
After set up again, reset the power supply.
Remove external noise around Signal Amplifier or
Network cable. (Keep enough distance)
2. Signal Amplifier (UTY-VSGX)
Cause 2 : Signal Amplifier is defective.
If normal voltage (Rated Voltage) is applied to power supply
terminal of Signal Amplifier,
there is a possibility of defective
PCB. Proceed as follows.
Replace Signal Amplifier.
OK
AC
Trouble shooting 59
Trouble shooting 60
04-65
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......