Protective Function
Detect Parts
Operating Condition
Operation
Overcurrent Break
Stop
(Compressor)
Overcurrent
Protection Circuit
COOL HEAT
Compressor stopped
Heatsink Temp
Thermistor
<Pattern starting condition>
Heat sink temperature 100°C
<Pattern reset condition>
3 minutes have elapsed and heat sink temperature 85°C
Compressor stopped
Heatsink Temp
Protection Stop
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and heat sink temperature 85°C
Compressor stopped
Error display
<Pattern starting condition>
Current value Cooling: 22.5A / Heating: 23.5A
<Pattern reset condition>
Current value Cooling: 22.5A / Heating: 23.5A
Frequency Maximum
Setting Protection
(Compressor)
<Pattern starting condition>
Current value Cooling: 23.0A / Heating: 24.0A
<Pattern reset condition>
Current value Cooling: 23.0A / Heating: 24.0A
Current Detector
Circuit
Compressor is stopped when the over currernt protectioncircuit in the
inverter PCBoad detects an abnormal current duringthe operation.
If it repeated 5 times, the compressor becomes permanentstop.
Compressor is stopped when the over current protection circuit in the
inverter PC Board detects an abnormal current at the time of start up.
Compressor becomes permanent stop if it repeated over the number
of set time.
<Reset condition>
Error reset (push button SW) executed after power turned on again.
Compressor speed lowered
Compressor speed rise prohibited
• Pattern and start current value changed by outside
temperature
DISPLAY
E941
E931
(permanent stop)
(permanent stop)
EAC4
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......