Trouble shooting 9
INDOOR UNIT Error Method:
Wired Remote Controller
Communication Error
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 1 2
Detective Actuators:
Indoor unit controller PCB circuit
Wired Remote Control
Detective details:
Upon receiving the signal more than 1 time from Wired Remote or other Indoor
unit, but the same signal has not been received more than 1 minute.
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of
controller
PCB Connector. (Power supply for Remote)
If DC12V, Remote Control failure (C
ontroller
PCB is OK) >>> Replace Remote
If DC0V, Controller PCB failure (Remote is OK) >>> Replace
Controller
PCB
-
In case of re-installation is done due to removed connector or incorrect
wiring, turn on the power again.
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
Trouble shooting 9
INDOOR UNIT Error Method:
Wired Remote Controller Token Error
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1, Error LED Continuous Flash.
Remote Controller : 1 2
Detective Actuators:
Indoor unit Controller PCB circuit
Wired Remote Control
Detective details:
More than 1 time of Token (Communication between wired remote controllers)
is received, but it was not received more than 1 minute.
OK
DC
Forecast of Cause :
1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
Forecast of Cause :
1. Terminal connection abnormal 2. Mis-setting 3. Wired Remote Control failure 4. Controller PCB failure
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
04-19
Cassette Type CN5 , AS*E 07,09,12,14LACH / AS*A 07,09,12,14LACH Type CN7 , Other CN17
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of Controller PCB Connector. (Power supply for Remote)
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote
lIf DC0V, Controller PCB failure (Remote is OK) >>> Replace Conroller PCB
In case of re-installation is done due to removed connector or incorrect
wiring, turn on the power again.
DC
Cassette Type CN5 , AS*E 07,09,12,14LACH / AS*A 07,09,12,14LACH Type CN7 , Other CN17
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......