2-2-1 Operation / Stop Condition
When cooling requirement capacity or heating requirement capacity from either of the indoor units in the same
refrigerant circuit is input, the compressor operates.
When all the indoor units in no "cooling requirement capacity" or "heating requirement capacity", the compressor
is stopped.
But in the following case, the compressor operates in accordance with operation of each mode.
During 3 minute restart prevention operation
Icing protection
Failure (Refer to
chapter 4, TROUBLE SHOOTING )
Under expansion valve initialization
At protective operation
Emergency stop
Defrost operation
02-02
2-2 COMPRESSOR OPERATION
2-2-2 Capacity Control
(1) Capacity of compressor operation
By the operation of DC inverter rotary compressor, the amount of required refrigerant circulation acceding to
cooling and heating load can be supplied from compressor efficiently.
DC inverter rotary compressor is able to control the amount of
required refrigerant circulation in details.
Cooling/Heating load
C
ap
ac
ity
o
f
co
m
pr
es
so
r o
pe
ra
tio
n
Total capacity
Peak cut stop operation
Oil recovery
Inverter Compressor
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......