EKI-6333AC-4GP User Manual
94
Mode
Select an expected data logging scheme for the data logging rule.
There are five available schemes:
Sniffer:
The Modbus gateway will record all the Modbus
transactions between the Master and Slave devices.
Off-Line Proxy:
When the connection between the Modbus
gateway and Master is lost, the predefined proxy rule will be
triggered and the Modbus gateway will issue specified
function code to collect and record the data / status from the
Slave devices
Full-Time Proxy:
The predefined proxy rule will be triggered
all the time and the Modbus gateway will issue specified
function code to collect and record the data / status from the
slave devices
Sniffer & Off-Line Proxy:
This is a mixed mode for both
Sniffer and Off-Line Proxy modes.
Sniffer & Full-Time Proxy:
This is a mixed mode for both
Sniffer and Full-Time Proxy modes.
Master Type
Specify the Modbus Master device to apply with the data logging
rule. It can be IP address for Modbus TCP Master, or local serial
port for local attached Modbus RTU/ASCII Master.
Master Query Timeout
(sec)
Specify the timeout value for querying Modbus Master. If no
response from the master for the specified timeout setting,
selected proxy rule will be triggered and applied with the data
logging rule.
Note:
If
Off-Line Proxy
scheme is selected, the timeout setting will
be used to check. Otherwise, it is a don’t care value.
Proxy Rules
Select the proxy rule to be applied with the data logging rule.
Note:
If any proxy scheme is selected, please create the required
Proxy rules in advance, and select from the list.
Enable
Check
Enable
checkbox to activate the data logging rule.
Save
Click
Save
to save the settings.
Undo
Click
Undo
to cancel the settings.