VistaKey Installation Guide
5–30
•
The user must be assigned to the partition. If not the user will not be accepted at the
keypad.
•
The user must be assigned to a card that has access to the point specified.
•
The user must have access to the partition at the time the command is entered.
To enable this feature, enter #93 Menu Mode Programming in the alarm system in
accordance with the procedures provided in your alarm system manuals. The following
message is displayed on the keypad:
ZONE PROG?
1=YES 0=NO
Press 1 to enter Zone Programming. The following screen appears.
NOTE: During programming, press [
✲
] to display the next screen.
Press [#] to display a previous screen.
Set to Confirm?
1=YES 0=NO
This prompt pertains to the confirmation of RF and polling loop
device serial numbers. When you are programming for the #73
function, the response to this entry does not affect programming.
Press either 1 or 0. The following screen appears.
ENTER ZONE NO.?
000 = QUIT
025
Zone 025 entered
↑
Enter the 3-digit zone number for the zone being programmed to
accept an access point command. As an example, 025 is being
shown here.
Press [
✲
] to accept the entry. The system advances to the summary
prompt below.
025 ZT P RC B IN
L
00 _ _ _ _ _ _ _
A display appears showing a summary of that zone’s programming.
ZT = Zone Type, P = Partition, RC = Report Code, B = Bell/Aux
Relay assignment for zone, IN = the input type of device, and L =
the device’s loop number to which the sensor is connected. Some
devices can support more than one zone by means of individual
loops. If the zone is not programmed, the display will appear as
shown here.
Press [
✲
] to continue.
025 ZONE TYPE
Press 27 for access point.
Press [
✲
] to accept the entry and continue.
025 Access
Point
(01-31)
00
Enter the 2-digit (01-15) door number for the VistaKey:
NOTE: The response to this question must be the address that was
set in the VistaKey module for the door (access point) being
programmed.
Press [
✲
] to continue.
025 Entry or Exit
Entry
0
Press 0 for Entry or 1 for Exit. The selection entered should match
(entry or exit) the access point being accessed. Note that this
affects the event that gets logged and reported so, you want to
select entry for an entry point and exit for an exit point.
Press [
✲
] to continue.
025 PARTITION
1
Enter the partition number that the access point is assigned to.
Press [
✲
] to continue.
Summary of Contents for VistaKey-SK