Assembling and Mounting the VistaKey-SK
To assemble and mount the VistaKey-SK, follow the procedure below:
1. Determine the mounting location for the VistaKey-SK. It must be mounted inside the
protected area near the door strike.
2. Remove the front cover from the VistaKey-SK panel.
3. Mount the Universal Mounting Plate (P/N K4555) in the VistaKey-SK cabinet by sliding
the tabs on the rear of the plate into the 3rd row of mounting points in the cabinet. See
Figure 4-2.
The Universal Mounting Plate is designed so that the tabs will hold it in the cabinet. If desired,
retaining screws (supplied) may be used in the middle 2 holes in the plate to attach the plate to
the cabinet more securely.
+
+
UNIVERSAL
MOUNTING
PLATE
P/N K4555
Figure 4-2: Installing the Mounting Plate
4. Position the cabinet on the wall and use the holes in the back of the cabinet to mark your
four mounting holes.
5. Using 4 anchors or fasteners (not supplied), mount the cabinet to the wall.
6. Mount the Power Supply (P/N SA12040) in the VistaKey-SK cabinet by sliding it into the
slots at the top of the cabinet. Secure the power supply using 3 screws, 3 black mounting
spacers, and 1 nylon washer (on the lower-right screw). See Figure 4-3.
Failure to use the nylon washer could result in a ground fault in your fire/burglary system.
Disabling the ground fault indication feature is subject to the local authority having jurisdiction.