Section 5 - Programming
5–7
Preparing an Event/Actions Worksheet
Event/actions are events used to activate outputs, bypass zones, etc. based on the events that
occur in the alarm system. There are 32 event/actions that may be programmed for the
system.
The actions that can be programmed to automatically occur due to (or as a result of) set
events are: relay commands, arm/disarm commands, zone bypassing commands, open/close
access conditions, and access control commands.
Fill out the Event/Action Worksheet (located at the end of this section) using the steps
outlined below:
As an aid to understanding the procedures for filling out the Event/Actions worksheet,
assume that you want to turn on a light (via relay # 1) on an access grant at access point 1,
and further assume that this is to occur between the hours of 08:00 AM and 05:00 PM (set via
time window 01) on Monday through Friday. As you perform the following steps, examples are
provided for filling out the worksheet.
1. Enter the Event No. listed in Table 5-2: Event Actions for the event desired.
Example: Enter Event No. 22 for an access point grant.
Days
Event
Event
No.
Event
Name
Event
Specifier
Action
No.
Action
Desired
Action
Specifier
Time Window
(00= Always, 01-20
= Time Window #)
M T W T F S S H
1
22
2
2. Enter the Event Name listed in Table 5-2: Event Actions for the event number.
Example: Enter AP Grt for event number 22.
Days
Event
Event
No.
Event
Name
Event
Specifier
Action
No.
Action
Desired
Action
Specifier
Time Window
(00= Always, 01-20
= Time Window #)
M T W T F S S H
1
22
AP Grt
2
3. Enter the Event Specifier that corresponds to the description in Table 5-2: Event
Actions.
Example: Enter 01 for access point number.
Days
Event
Event
No.
Event
Name
Event
Specifier
Action
No.
Action
Desired
Action
Specifier
Time Window
(00= Always, 01-20
= Time Window #)
M T W T F S S H
1
22
AP Grt
01
2
4. Enter the Action No. listed in Table 5-1: Action Codes for the action desired.
Example: Enter Action No. 01 for relay on.
Days
Event
Event
No.
Event
Name
Event
Specifier
Action
No.
Action
Desired
Action
Specifier
Time Window
(00= Always, 01-20
= Time Window #)
M T W T F S S H
1
22
AP Grt
01
01
2
5. Enter the Action Name listed in Table 5-1: Action Codes for the action number.
Example: Enter Relay On for action number 01.