VistaKey Installation Guide
5–12
00 = Assign for Unused Zones
09 = Fire Without Verification
④
01 = Entry/Exit #1, Burglary
10 = Interior Delay, Burglary
02 = Entry/Exit #2, Burglary
16 = Fire With Verification
④
03 = Perimeter, Burglary
17 = Fire Waterflow
④
04 = Interior Follower, Burglary 18 = Fire Supervisory
④
05 = Trouble Day/Alarm Night
19 = 24-Hour Trouble
06 = 24-Hr. Silent Alarm
23 = No Alarm Response
07 = 24-Hr. Audible Alarm
(e.g., relay activation)
08 = 24-Hr. Auxiliary
29 = Momentary Exit
⑤
①
Zone type 01 or 02 is recommended for the typical DSM and
DSMB zones to obtain an entry/exit delay. If a delay is not
desired, zone type 03 is recommended.
②
DO NOT assign a response type to the RTE zone when it is
being used as a request to exit (controlling a door strike or mag
lock). A response type may only be assigned when the RTE is
NOT being used as a request to exit, which makes it an
uncommitted zone. As an uncommitted zone, it may be assigned
a response type for use as another type of zone.
③
In installations requiring supervision of the cabinet cover, the
general purpose zone should be programmed as tamper (choose
zone type 05).
④
These fire zones cannot be used in UL Installations.
⑤
Refer to “Momentary Exit Access Points” in this section for a
complete description of Momentary Exit.
Press [
✲
] to accept the entry and continue.
010 PARTITION
2
Enter the partition number you are assigning this zone to. The
partition number assigned should be the same partition number as
the one assigned to the protected area that the door (access point) is
allowing entry to.
Press
[
✲
]
to continue.
010 REPORT CODE
1
st
03 2
nd
12
3C
Enter the report code. The report code consists of 2 hexadecimal
digits, each in turn consisting of 2 numerical digits. For example, for
a report code of “3C,” enter 03 for 3 and 12 for C.
NOTES:
•
Entering 00 disables the reporting of all zone-related events. For a
DSM input type, these are events like 423,46, 427, etc. and any
report code that would normally be sent dictated by the zone type
selection. (See Event Log section of this manual for a complete
listing of ACS events). For a GP or uncommitted RTE zone, it
disables reporting for all zone related events.
Entering 00 overrides any ACS Dialer selections that may be
enabled.
•
If will be be using the ACS Report codes (ACS Dialer Events
enabled), the zone report code must be set to a non-zero value.
•
If ACS Dialer Events are being enabled, you must use the Contact
ID reporting format.
Summary of Contents for VistaKey-SK
Page 2: ......
Page 6: ...vi...
Page 8: ...viii...
Page 40: ...VistaKey Installation Guide 4 10...
Page 107: ......
Page 108: ...165 Eileen Way Syosset New York 11791 Copyright 2000 PITTWAY CORPORATION l K4005 6 00...