Technical Data
89/ 122
Powerlift prefabricated pumping station
H3, H4, T
Basin
and T
= Construction height with joints for circular rotating mechanical seal (15 mm) or mortar
(10 mm)
H maximum = Maximum installation depth of the tank relative to the tank base
EL = Ventilation pipe connection DN 100/OD = 110 mm: details for pipe bottom on request
KL = Blank cable pipe connection DN 100/OD = 110 mm: details for pipe bottom on request
¹
)
For connecting pipe OD 63 mm
²
)
Flange connection with flange connection dimension according to DIN 2501– PN 16
6.1.2 Key data
Prefabricated pumping
station
Useful vol-
ume
Weight
Model
Manhole base
section
Cover plate
Complete
*
Complete
[l]
[kg]
[kg]
PSD-P-1000/T
Basin
685
210 – 510
1,040
425
PSD-B-1000/T
Basin
480
370 – 670
2,450
625
PSD-B-1000/T
Basin
1,070
45 – 240
2,450
625
PSD-B-1500/T
Basin
395
810 – 1,390
5,100
1,230
PSD-B-1500/T
Basin
795
105 – 690
5,100
1,230
PSD-B-2200/T
Basin
515
2,600 – 3,910
7,250
2,510
PSD-B-2200/T
Basin
505
2,650 – 3,950
7,500
2,510
PSD-B-2200/T
Basin
585
3,590 – 4,200
8,510
2,510
*
without submersible pumps