Installation
53/ 122
Powerlift prefabricated pumping station
Î
Pull the connecting cable for the level
probe upwards (not while energised) until
it reaches the chain holder.
Î
Place the loop around the cable eye (
●
)
and fasten with cable tie.
Î
Hang the cable eye on the chain holder.
Î
Utilise the pull wire to pull the connecting
cable together with the pump connecting
cable through the cable duct up to the
assembly location of the control.
Î
Keep sufficient excess cable length
(approx. 1 m), to enable the wiring in the
terminal compartment of the control.
This is the only way that the level probe can be