Commissioning
71/ 122
Powerlift prefabricated pumping station
4.3.2 Powerlift PSD-B-1000 with T
Basin
= 480
Menu
point
Unit
Pump type
Settings with level sensor:
A
+
B
C
D
E
AL
PL
BL
OFF
AL
PL
BL
OFF
AL
*
PL
*
BL
*
OFF
*
Flood AL
=
AL
Peak load
ON =
SL
Base load
ON =
BL
Base load
OFF =
OFF
cm
SAT-100/D
101 91 81 11 119 109 99 18
–
101 91 81 11
SAT-150/D
101 91 81 11 119 109 99 18
101 91 81 11
SAT-200/D
101 91 81 11 119 109 99 18
101 91 81 11
SAT-50/2/32/D
101 91 81 11 119 109 99 18
101 91 81 11
SAT-75/2/32/D
101 91 81 11 119 109 99 18
101 91 81 11
SAT-V 75/2/50/D
96 86 76 11 119 109 99 23
96 86 76 11
SAT-V 150/2/50/D
96 86 76 11 119 109 99 23
96 86 76 11
SITA 150 N-ex
99 89 79 11 119 109 99 20
99 89 79 11
SITA 200 N-ex
99 89 79 11 119 109 99 20
99 89 79 11
SITA 300 N-ex
90 80 70 11 119 109 99 29
90 80 70 11
SITA 550 N-ex
83 73 63 11 119 109 99 36
83 73 63 11
After-running
period
s
0
**
0
0
0
Maximum
current
– 1
***
Maximum
current
– 2
***
A
SAT-100/D
2.3
SAT-150/D
2.7
SAT-200/D
3.6
SAT-50/2/32/D
1.1
SAT-75/2/32/D
1.3
SAT-V 75/2/50/D
1.3
SAT-V 150/2/50/D
2.6
SITA 150 N-ex
2.9
SITA 200 N-ex
3.7
SITA 300 N-ex
5.1
SITA 550 N-ex
8.7
Level
control
–
Internal converter
Float
switch
4-20mA
interface
20 mA =>
level
cm
–
–
–
400
Language
–
German
*
Previously set under “level control” menu item = Set
4-20mA Interface
“and under”
20 mA => Level =
400
.
**
Value = 0 with version with air bubble injection. With version without air bubble injection, value assessment
during trial run: Water level must remain approx. 5 cm under lower edge of back pressure hole.
***
With Level Control PS 2 Control System: Setting via separate motor protection switch.