Commissioning
66/ 122
Powerlift prefabricated pumping station
1 = Rotaryknob for “Display”
2 = Display
3 = Button for “Manual” (P1 and/or P2)
4 = Button “0” (P1 and/or P2)
5 = LED red “Malfunction P1 and/or P2 arranged”
6 = LED yellow “Operation/After-running” (P1 and/or
P2)
7 = LED red “Flood alarm”
8 = LED red “Malfunction, general”
9 = LED green “Automatic/Manual mode” (P1 and/or
P2)
10 = Housing
11 = Main switch
12 = Button “Auto” (P1 and/or P2)
13 = Button “Acknowledge selection”
Function of the controls
Description
Function
Explanation
Display
Selection of the
menu items
The rotary knob can be used to select the menu items in the display
panel.
The display automatically changes back to the basic setting after 20
seconds.
Selection
Acknowledge
Acknowledge
malfunction
The button is used to acknowledge malfunction signals and messages
after removing the cause of the fault.
If the malfunction is not corrected, only the group fault alarm relay and
the alarm sound signal (e.g. flood alarm) are switched off.
Confirm setting
The button is used to save the settings made in the menu items.
MANUAL
Switch on manual
operation
The buttons for Pump P1 and P2 are used to switch on the pumps
independently of the “level switching”.
Manual operation is switched off automatically after 2 minutes.
0
Switch off operation
The buttons for Pump P1 and P2 are used to switch off automatic mode
or manual operation of the pumps.
AUTO
Switch on
automatic mode
The buttons for Pump P1 and P2 are used to switch on automatic
operation of the pumps and to control them automatically via the “level
switching”.
Main switch
Switch on power
Thee main switch enables the electrical equipment to be connected with
all poles to the electrical supply .
Explanation of the display elements
Description
Meaning
Explanation
Malfunction
Pump P1 or P2
malfunction
Malfunction
Pump(s) not in operation
Flood
alarm
Flood alarm group
fault
Fault signal: The water level in the tank has reached the “Flood alarm”
level
Malfunction
Malfunction,
general
All malfunctions will be displayed
Operation
after-running
Operating display
for Pump P1 or P2
LED illuminates: Pump(s) in operation
LED flashes: Pump(s) in operation via the after-running function