Phase rotation within a charging group |
31
WARNING!
Checking the connection
Please ensure that the conductors that are pre-fixed to the terminals remain attached correctly after connecting
the power supply cable.
DANGER!
Dangerous electrical currents
The electronic components of your wallbox will be damaged if a voltage above 250 V is applied between the L1
current-carrying conductor and neutral!
Phase rotation within a charging group
To avoid a phase imbalance in a charging group, the phase rotation must be adjusted according to the following dia-
gram during the electrical installation of the Wallbox eM4 Twin:
Wiring diagram
Wallbox 1, 4, 7 etc.
Wiring diagram
Wallbox 2, 5, 8 etc.
Wiring diagram
Wallbox 3, 6, 9 etc.
L1
L2
L3
N
L1
L2
L3
N
PE
#1
L1
L2
L3
N
L2
L3
L1
N
PE
#2
L1
L2
L3
N
L3
L1
L2
N
PE
#3
Wallbox
eM4 Twin – 1
eM4 Twin – 2
eM4 Twin – 3
Terminal block
L1
L2
L3
N
PE
L1
L2
L3
N
PE
L1
L2
L3
N
PE
Supply
L1
L2
L3
N
PE
L2
L3
L1
N
PE
L3
L1
L2
N
PE
Wallbox
eM4 Twin – 4
eM4 Twin – 5
eM4 Twin – 6
Terminal block
L1
L2
L3
N
PE
L1
L2
L3
N
PE
L1
L2
L3
N
PE
Supply
L1
L2
L3
N
PE
L2
L3
L1
N
PE
L3
L1
L2
N
PE
Wallbox
eM4 Twin – 7
eM4 Twin – 8
eM4 Twin – 9
Terminal block
L1
L2
L3
N
PE
L1
L2
L3
N
PE
L1
L2
L3
N
PE
Supply
L1
L2
L3
N
PE
L2
L3
L1
N
PE
L3
L1
L2
N
PE
...
NOTE
Phase rotation in a single-phase mains system
The connection diagram shown above applies to 3-phase mains systems. If you are using a single-phase mains
system, the
L1
supply cable must always be connected in each wallbox!