2
132
Tru O N E® AT S , I N S TA LL ATI O N A N D O PER ATI N G I N S TR U C TI O N
Automatic
transfer switch
Lug assembly
LOAD
SOURCE S2
SOURCE S1
OX_30...100_
OZXA-100
OZXA-100
OZXA-24
OX_30...200_
OZXA-200
OZXA-200
OZXA-25
OX_260/400_
OZXA-400
OZXA-400
OZXA-26
OX_600_
OZXA-800E
OZXA-800E
OZXA-800L
OX_800_
OZXA-800S / OZXA-800E
OZXA-800S / OZXA-800E
OZXA-30
OX_1000/1200_
OZXA-1200
2 x OZXA-800S (_E)
OZXA-1200
—
Table 8.7 OX_30...1200_ / suitable lug assembly
Automatic
transfer switch
Max. distance from switch frame to nearest cable/busbar support
SOURCE [in / mm]
LOAD [in / mm]
OX_30...200_
11.8 / 300
5.9 / 150
OX_260_
11.8 / 300
5.9 / 150
OX_400_
11.8 / 300
5.9 / 150
OX_600_
11.8 / 300
5.9 / 150
OX_800_
15.7 / 400
7.8 / 200
OX_1200_
15.7 / 400
7.8 / 200
—
Table 8.8 OX_30...1200_/ cable/busbar support with breaker or fuses (SCPD)
OZXA-30, OZXA-1200
OZXA-100...400, OZXA-800E, OZXA-800S
OZXA-24...26, OZXA-800L
SOURCE 2 (S2)
SOURCE 1 (S1)
LOAD