3 4 OX _ 3 0 -16 0 0 rev. B / 1 S CC 3 0 3 01 1 M 0 2 01
8.2.2
Wiring of OX_800U…1600 /
busbar connections and cable lugs
—
Fig. 8.5 OX_800U…1600, busbar connection
—
Fig. 8.6 OX_800U…1600, wiring / cable lugs
A0
7488
4×
4×
A0
7488
Automatic
transfer
switch
Bolt
size
Tightening
torque
[Nm / lb.in]
OX_800U…1600_
M12
50…75 / 443…664
—
Table 8.4 OX_800U…1600_/ bolt
size and tightening torque
Automatic
transfer
switch
Max. distance from
switch frame to nearest
cable/busbar support
SOURCE
[mm / in]
LOAD
[mm / in]
OX_500...800_
300 / 11.8
150 / 5.9
- Busbar
225 / 8.9
150 / 5.9
OX_800U...1600_
400 / 15.7
200 / 7.8
—
Table 8.5 OX_500…1600_/ cable/busbar
support with breaker or fuses (SCPD)
General warning
The cable lug must be pushed into the oval
hole of the terminal as close as possible to the
switch pole.