Settings (*Default)
Description
Modules (Optional modules)
Ekip Signalling 2K-1 / -2 / -3
I 11/12, I 21/22, I 31/32
Function No Function*
Input disabled
Emergency Stop
Transfers to O position in delayed transition I-O-II type
switches. Disables automatic control mode in both
delayed and open transition types.
Remote Test on Load
Start/stop test on load sequence in rising (NO) or falling
(NC) edge of the input signal.
Remote Test off Load Start/stop test off load sequence in rising (NO) or falling
(NC) edge of the input signal.
Inhibit AUTO Mode
Prevent switch control operations, configuration, test
sequences and generator start in case of priority source
failure.
Manual Retransfer
Disables automatic transfer back to priority source.
Source Priority S1
Sets priority for source 1 in transformer-transformer
application.
Source Priority S2
Sets priority for source 2 in transformer-transformer
application.
Inhibit Transfer
Disables automatic transfer from priority source to non-
priority source.
Bypass Running Time
Delays
Bypass any currently running time delay.
Remote Control to S1
Transfer to S1 when active. Overridden by activated
'Remote Control to OFF' signal.
Remote Control to OFF Transfer to position O when active.
Remote Control to S2
Transfer to S2 when active. Overridden by activated
'Remote Control to OFF' or 'Remote Control to S1'
signals.
Reset Alarm
Reset any active switch control alarms (open I failure,
close I failure, open II failure, close II failure).
Manual-Auto Mode
Toggle automatic/HMI control mode, input is active only
in rising/falling edge according to contact type.
Contact
Type
NC
Active open
NO*
Active closed
O 11/12, O 21/22, O 31/32
Function No Function*
Output disabled
Alarm/Product
Availability
Signals any active alarms or ATS being disabled for
automatic transfer operations.
Load Connected to S1
Switch in position I.
Load Disconnected
Switch in position O.
Load Connected to S2
Switch in position II.
Pre-transfer Signal
Signal is activated and transfer is delayed according to
pre-transfer delay. Signal is kept activated according to
post-transfer delay after transfer.
Continued on the next page