5.6.5.1 Signallings
The following table illustrates the possi-
ble signals, and their meaning:
Link
Activity
LED
Indication
Description
Power LED, green
Off
Power supply absent.
On fixed
Power supply and communication
with the device present.
On, with two quick flashes per second
Power supply present, and
communication with device absent.
Link LED, green
Off
Connection error (signal absent).
On, fixed
Correct connection.
Activity LED, yellow
Off
No activity on the line.
On, flashing
Activity present on the line (in
reception and/or transmission.
—
Table 5.20 Indication / Ekip Com Profinet -module
—
Fig. 5.23 Signals of Ekip Com Profinet -module
The following table illustrates the ports
used by the module:
Ethertype
Port
Service
Notes
0x88CC
-
LLDP
Link Layer Discovery Protocol
0x8892 (Profinet)
-
Profinet IO
Specific for real time
communications (RT)
0x0800
34964/udp
Profinet-cm
(Context Manager)
DCE/RP
—
Table 5.19 Ports of Ekip Com Profinet –module