Tru O N E® AT S , I N S TA LL ATI O N A N D O PER ATI N G I N S TR U C TI O N
1
Automatic transfer switch, power circuit
Value
Rated operational voltage U
200…480 Vac
Rated frequency f
50 / 60 Hz
Rated impulse withstand voltage U
imp
12 / 8 kV
Operating times
See Table 7.2
Automatic transfer switch, control circuit
Value
Remark
Voltage supply
200…480 Vac
Integrated, see Fig. 7.1
Operating voltage range
±20%
Voltage measurement accuracy
Rated frequency f
50 / 60 Hz
Operating frequency range, Level 2
±10%
Level 2 = HMI with DIP-switches
Operating frequency range, Level 3 and 4
±20%
Level 3 = HMI with LCD screen,
Level 4 = HMI with touch screen
Frequency measurement accuracy
Rated impulse withstand voltage U
imp
6 kV
U/SOURCE 1
Operating voltage for
control circuit
200...480 Vac.
Generator supply; min.
power rating 20 kVA.
U/SOURCE 2
—
Fig. 7.1 Power supply for control circuit, in figure type OX_B (source on bottom)
—
7. Technical data