6.2 Warnings
LCD
Touch
Message
Reason
S1 and S2 not in sync
Voltage sources are not synchronized
Voltage Not Calibrated
Calibration data in power module is invalid or unavailable
Current Not Calibrated
Calibration data in current measurement module is invalid or unavailable
Pole temperature warning
Measured pole temperature is near the alarm level
Control Retry
Failed transfer sequence retry activated
Auto Control Disabled
Device is in manual operating mode
Local Bus
Module heartbeat error
Configuration
Configuration session ports are open
RTC capacitor charging
Real time clock is not yet operational, date & time setting is disabled as
long as this warning is active. RTC capacitor is charged from source
voltage (not AUX) and takes about 10 minutes
—
Table 6.2
Warnings-list in level 3 and 4, LCD and touch control interfaces