63
3 4 OX _ 3 0 -16 0 0 rev. B / 1 S CC 3 0 3 01 1 M 0 2 01
1
TO
U
C
H
Parameters (continued)
*Default
Device Parameters (continued)
Voltage & Frequency Setpoints
Defines the voltage and frequency limits for
source being acceptable. Source has an anomaly
when measured voltage/frequency goes out of
range drop-out lower/drop-out Upper. Source
becomes acceptable when measured voltage/
frequency goes back in range pick-up lower/
pick-up higher.
S1 Setpoints
S1 Drop-out
Voltage
Upper Threshold
102...120 % Un (115* % Un)
Lower Threshold
70...98 % Un (85* % Un)
S1 Pick-up
Voltage
Upper Threshold
101...119 % Un (114* % Un)
Lower Threshold
71...99 % Un (86* % Un)
S1 Drop-out
Frequency
Upper Threshold
101...120 % fn (115* % fn)
Lower Threshold
80...99 % fn (85* % fn)
S1 Pick-up
Frequency
Upper Threshold
100.5...119.5 % fn (114* % fn)
Lower Threshold
80.5...99.5 % fn (86* % fn)
S2 Setpoints
S2 Drop-out
Voltage
Upper Threshold
102...120 % Un (115* % Un)
Lower Threshold
70...98 % Un (85* % Un)
S2 Pick-up
Voltage
Upper Threshold
101...119 % Un (114* % Un)
Lower Threshold
71...99 % Un (86* % Un)
S2 Drop-out
Frequency
Upper Threshold
101...120 % fn (115* % fn)
Lower Threshold
80...99 % fn (85* % fn)
S2 Pick-up
Frequency
Upper Threshold
100.5...119.5 % fn (114* % fn)
Lower Threshold
80.5...99.5 % fn (86* % fn)
Continued on the next page