Tru O N E® AT S , I N S TA LL ATI O N A N D O PER ATI N G I N S TR U C TI O N
—
9.2 Phase barriers
Phase barriers must be used to maintain a
clearance of 1 inch on the automatic
transfer switch types.
These are not required with the standard
UL mechanical lug offering, but may be
—
Fig. 9.2 Mounting of phase barriers, type OXEB_
A07
4
91
OXEB_
required when alternate connections do
not have anti-rotation features, or when
alternate connections reduce over-air
clearance between phase conductors to
less than 1 inch.