124 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Additional functions | 2 - Load Shedding
Ekip Touch Measure
A specific page containing the main measurements is available in the
Measurements
pages, with
Power
Controller
activated:
Measurement
Description
F
Frequency measured
Fn
Nominal frequency of the Trip unit
LOADS
Number of loads monitored
LOADS Shed
Number of shed loads
The
Power Controller
menu, with information concerning the 15 loads in two submenus, is available in the
About
page when
Load Shedding
is activated (page 34).
Submenus
Information provided
Load Input Status
Status of the loads (from Load 1 to Load 15): open or closed
Load Active
Load configuration (from Load 1 to Load 15): active or inactive