ABB | SACE Tmax XT
Settings | 1 - Main settings
115 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Modules
The
Modules
menu provides various options:
Parameter
Description
Default
Local/Remote
The parameter defines the mode in which the parameters are written in the
unit:
•
Local
: parameter editing only via the display or service connector
•
Remote
: parameter editing only remotely (Ekip Com modules)
NOTES
:
•
the Remote mode requires the presence of auxiliary power supply
and Ekip Com modules, otherwise it disables automatically
•
However, the Local/Remote parameter can still be edited in the
Remote mode
Local
Local bus
The parameter enables communication between the Trip unit and modules
installed via terminal box or outside the unit to be activated.
Correct communication between unit and modules is confirmed by:
• population of the
Modules
menu with all the modules connected
• Power Leds of the modules on and synchronized like the power led of
Ekip Touch
• absence of Local Bus alarm in the diagnosis bar
Off
Ekip Signalling
1K
Menu with the parameters of the module (page 194)
Ekip Measuring Menu with the parameters of the module (page 128)
BLE
BLE activation parameters, see next paragraph
Off
-
Menu of every module connected and detected (from page 132)
Functions
Access to the
LOCAL Switch On
and
RESET signaling
functions (from page
BLE - Connection security
Activation of LV communication requires the Trip unit to be pre-engineered for a wireless connection: security
of the data and LV connection between the Trip unit and its device is guaranteed thanks to the
ABB Ekip
Connect Mobile
application and the pairing configuration.
WARNING!
•
It is the customer's sole responsibility to provide and continuously ensure a secure
connection between his device and the Trip unit. The plant manager must establish
and maintain appropriate measures (such as but not limited to the installation of
malware prevention systems, application of authentication measures, his own system
and interface against any kind of security breach, unauthorized access, interference,
intrusion, loss and/or theft of data or information. ABB and its affiliates are not liable
for damages and/or losses related to such security breaches, unauthorized accesses,
interference, intrusion, loss and/or theft of data or information, use of APPs other than
those allowed.
•
Consult the guidelines of the Ekip Connect Mobile APP for the correct pairing procedure
ABB recommends a few general configurations to strengthen the access of data into the Trip unit:
• activate the access PIN code in the Trip unit configure it with a value differing from the default value
• if parameters need not be written, configure the Trip unit only for parameter readout via bus (
Test bus
parameter =
Off
)
• switch off the BLE (
BLE-Enable
parameter =
Off
) after use
IMPORTANT: communications via LV and via service connector function alternatively:
if BLE is activated there can be no communication with other accessories via the
service connector