ABB | SACE Tmax XT
192 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Internal accessories | 7 - Ekip Com Hub
Power supply
Ekip Com Hub is supplied directly by the
Ekip Touch
to which it is connected.
NOTE:
communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Configurations via menu
Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the
Settings
menu (page 33).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the
Settings
-
Modules
menu:
Parameter
Description
Default
Enable
Switches communication between module and server on/off.
Force Static IP
Address ON
Defines whether the module has the dynamic (Off) or static (
On
) IP
address.
If =
On
all the associated parameters are enabled
Off
Static address
IP address
Enables the static IP to be selected
0.0.0.0
Static Network
Mask
Enables the subnet mask to be selected
0.0.0.0
Static Gateway
address
When there are several subnets, enables the IP address of the node to
which the module is connected to be selected
0.0.0.0
Enable SNTP
client
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled.
Off
SNTP Server
Addr.
Allows the network server that supplies the SNTP to be set.
0.0.0.0
Password
code required to register module on Cloud
---
Remote
firmware update
Enables the firmware of the module to be updated. There are two
parameters:
•
Enable
, to configure firmware download
•
Automatic
, to automate module updating
Off
Automatic
Information in menu
The following information will be available in the
About
-
Modules
menu if Ekip Touch has detected the module
correctly:
Information
Description
SN and version
Identifier and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at the time of
connection to the network in the case of configuration with a dynamic IP, or can be
set via the menu in the event of a static IP.
NOTE:
without a DHCP server, the module automatically adopts a random IP
address within the 169.254.xxx.xxx
range
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which the modules
belong and enables modules to be searched for within a defined set of recipients.
Gateway address
IP address of the node to which the module is connected, in the presence of several
subnets
MAC address
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device