ABB | SACE Tmax XT
188 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Internal accessories | 6 - Ekip Link
Power Controller
Using the
Power Controller
function, each actor can:
• Acquire the status and control the loads
• Act as master and collect the energy measurements of actors entered as Energy Meters.
• Supply energy measurements to actors entered as masters
The state of the loads can be acquired by checking the status of the inputs of the signaling modules
connected to the actors of which the IP Addresses have been entered, while load control can be performed
by programming the outputs.
Remote acquisition of the statuses of the loads and their control can also be performed with
Ekip Signalling
10K
connected to the network.
Further details about the potential of the function are available in White Paper
management with Ekip Power Controller for SACE Emax 2".
Zone selectivity
With the Zone Selecitivity function:
• the IP addresses entered refer to actors with the role of interlock with respect to the current role
• the protections for which selectivity must be actuated by setting a mask, must be selected for each interlock
actor entered. Thus set, the function will now be indicated as logic in the following text so as to distinguish
it from the standard function, now also indicated as hardware in the following text
• thus selected, the protections add to those of the hardware S, G, D-Backward and D-Forward
• hardware selectivity only, or both hardware and logic selectivity can be selected
• diagnosis can be set, for each interlock release, to ascertain whether there is consistency between the
hardware and logic selectivity information
• a mask can be set for the purpose of identifying those protections whose received selectivity information
must be re-transmitted, regardless of whether the actor is in the alarm status. The mask is only applicable
to logic selectivity information
For further details about the Zone Selectivity function with
Ekip Link
, please consult page page 77.
Power supply
Ekip Link is supplied directly by the
Ekip Touch
to which it is connected.
NOTE:
communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Configurations via menu
Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the
Settings
menu (page 33.
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the
Settings
-
Modules
menu:
Parameter
Description
Default
Static IP address ON
Defines whether the module has a dynamic (Off) IP address
or static (On) IP address
Se = On all the associated parameters are enabled
Off
Static address IP address
Enables the static IP to be selected
0.0.0.0
Static Network Mask
Enables the subnet mask to be selected
0.0.0.0
Static Gateway address
When there are several subnets, enables the IP address of
the node to which the module is connected to be selected
0.0.0.0