ABB | SACE Tmax XT
Interface and menus | 3 - Graphic pages
29 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Continued from the previous page
Ekip Touch configuration involves certain exceptions:
• the Ne current measurements are available with 4P and 3P + N configurations
• the phase voltage measurements are available with the 4P configuration
• with the 3P configuration, pages:
Active Power, Reactive Power and Apparent Power
are replaced by the
Powers
page with the total active, reactive and apparent power measurements
• Ige/Rc current available with external sensor activated
•
Power Controller
page available with Power Controller function activated
•
Load Shedding
available with Load Shedding function activated
Press the sides of the display to browse the pages; press the
HOME
key to quit.
NOTE: each page can be set as the main page by pressing HOME
, holding it for five
seconds and confirming the message on the display
Diagnosis bar and Alarm list
The Diagnosis bar lists the faults detected by the unit. It shows a detail of each alarm for about two seconds.
Figure 19
Select the bar to access the
Alarm List
page, with the list of alarms present.
Figure 20
NOTE:
the Alarm List page also appears when the iTEST button is pressed in the cases
provided for and described on page
Each signal is followed by an icon that identifies the type of alarm:
Icon
Alarm type
Alarm
Warning, error or prealarm
About
Timing due to tripped protection
The complete list of alarms is given on page 19.