ABB | SACE Tmax XT
154 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
External accessories | 11 - Ekip Link
Zone selectivity
With the Zone Selecitivity function:
• the IP addresses entered refer to actors with the role of interlock with respect to the current role
• the protections for which selectivity must be actuated by setting a mask, must be selected for each interlock
actor entered. Thus set, the function will now be indicated as logic in the following text so as to distinguish
it from the standard function, now also indicated as hardware in the following text
• thus selected, the protections add to those of the hardware S, G, D-Backward and D-Forward
• hardware selectivity only, or both hardware and logic selectivity can be selected
• diagnosis can be set, for each interlock release, to ascertain whether there is consistency between the
hardware and logic selectivity information
• a mask can be set for the purpose of identifying those protections whose received selectivity information
must be re-transmitted, regardless of whether the actor is in the alarm status. The mask is only applicable
to logic selectivity information
For further details about the
Zone Selectivity
function with
Ekip Link
, please consult page 77.
Connections
For references about the connection and terminals, please consult document
; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication bus.
To connect the module to
Ekip Supply
and
Ekip Cartridge
, please consult documentTo connect the module
to Ekip Touch, please consult document
.
Power supply
Ekip Link
is supplied directly by the Ekip Supply module to which it is connected.
NOTE:
communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Interface
the module has three signaling leds:
1
2
Figure 50
LEDs
Description
Power
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Link (
1
)
Indicates the communication state:
• off: incorrect connection, signal absent.
• on steady: connection correct
Activity (
2
)
Indicates the communication state:
• off: no activity on line
• flashing: activity on line present (receiving and/or transmitting)