ABB | SACE Tmax XT
Internal accessories | 6 - Ekip Link
189 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Information in menu
The following information will be available in the
About
-
Modules
menu if Ekip Touch has detected the module
correctly:
Information
Description
SN and version
Identifier and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at the time of
connection to the network in the case of configuration with a dynamic IP, or can be set
via the menu in the event of a static IP.
NOTE
:
without a DHCP server, the module automatically adopts a random IP
address within the 169.254.xxx.xxx
range
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which the modules
belong and enables modules to be searched for within a defined set of recipients.
Gateway
address
IP address of the node to which the module is connected, in the presence of several
subnets
MAC address
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information
Description
Default
Client/Server
Parameter for changing the configuration of the module from Server
Only to Client and Server and for integrating it into an interactive data
exchange network (see Ekip Com Hub on page 191).
IMPORTANT: if Client/Server, the module allows data
exchange like a normal Server function
Server only
Enable IEEE 1558
Allows the IEEE 1588 protocol for distribution of the clock and
synchronization signal to be enabled
(1)
.
Off
IEEE 1558 Master
Enables the module to be set up as a master in the the network
segment to which it belongs (synchronization clock).
Off
IEEE 1558 Delay
mechanism
Allows the data exchange mode between module and master, either
Peer-to-Peer or End-to-End, to be selected.
End-to- End
Enable client SNTP
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled
(1)
Off
ANTP Server
address
Allows the network server that supplies the SNTP to be set.
0.0.0.0
Time zone
Defines the time zone to be used for synchronism
+00:00
Daylight Saving
Time
Used to select whether daylight saving time is present (ON) or not
(OFF) in the country to which the synchronization time refers
Off
Disable Gratuitous
ARP
Permits (Enabled ARP) the periodic generation of a Gratuituos ARP
message, used by Ekip Connect to rapidly find the modules via
Ethernet scan without knowing the IP address beforehand
ARP Enabled
Password protected
access
Enables the writing operations performed via the network to be
protected by a password (Request password)
Standard
mode
Password Modbus
TCP
With access protected by enabled password, this is the password to
use before each writing session
(2)
.
Local access
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2)
the parameter can only be changed via system bus in the remote configuration