-3U
0
Operate area
3I
0
RCADir
= 0º
ROADir
= 80º
IEC06000652-3-en.vsd
IEC06000652 V3 EN-US
Figure 45:
Example characteristic
Non-directional earth fault current protection
SEMOD175060-117 v10
Procedure
1.
Measure that the operate current is equal to the
INNonDir>
setting.
The function activates the START and STDIRIN output.
2.
Measure the operate time of the timer by injecting a current of 200% of the
operate value.
3.
Compare the result with the expected value.
The expected value depends on whether definite time
tINNonDir
or inverse
time was selected.
4.
Continue to test another function or complete the test by setting the test mode
to
Off
.
Residual overvoltage release and protection
SEMOD175060-131 v6
Procedure
1.
Measure that the operate voltage is equal to the
UN>
setting.
The function activates the START and STUN signals.
2.
Measure the operate time by injecting a voltage 1.2 times set
UN>
operate
value.
3.
Compare the result with the set
tUN
operate value.
4.
Inject a voltage 0.8 ·
UNRel>
and a current high enough to operate the
directional function at the chosen angle.
5.
Increase the voltage until the directional function is released.
6.
Compare the measured value with the set
UNRel>
operate value.
Section 11
1MRK 505 378-UEN A
Testing functionality by secondary injection
182
Line differential protection RED670 2.2 IEC
Commissioning manual
Summary of Contents for RED670 Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Page 2: ......
Page 18: ...12 ...
Page 36: ...30 ...
Page 68: ...62 ...
Page 72: ...66 ...
Page 108: ...102 ...
Page 278: ...272 ...
Page 282: ...276 ...
Page 288: ...282 ...
Page 306: ...300 ...
Page 307: ...301 ...