X1Zx+XNZx
X
R (Ohm/loop)
50%
80%
1
2
3
4
5
6
7
8
9
10
11
80% of RLdFw
40% of RLdFw
RFPEZx
12
13
alt. 80% of
RFPEZx (Load
encroachment)
120°
20°
a
IEC05000369-4-en.vsdx
IEC05000369 V4 EN-US
Figure 34:
Distance protection characteristic with test points for phase-to-
earth measurements
Table
is used in conjunction with figure
.
Table 31:
Test points for phase-to-earth L3-E (Ohm/Loop)
Test point
Reach
Value
Comments
1
X
(2 x X1
set
+X0
set
)/3
R
0
2
X
(2 x X1
set
+ X0
set
)/3
R
2 x R1
set
+ R0
set
)/3
3
X
0.8 x (2 x X1
set
+ X0
set
)/3
R
0.8 x (2 x R1
set
+ R0
set
)/3
+RFPEZx
set
4
X
0.5 x (2 x X1
set
+ R0
set
)/3
R
0.5 x (2 x R1
set
+R0
set
)/3 +
RFPEZx
set
5
X
0.85 x RFPEZx
set
x tan(ArgLdset)
ArgLd = angle for the maximal load
transfer
R
0.85 x RFPEZx
6
X
RLdFwset x tan(ArgLdSet)
R
RLdFw
set
7
X
0
R
RLdFw
set
8
X
–02143 x RLdFw
set
Exact: 0.8 x RFPEZx x tan
(ArgDir=20°)
R
0.8 x RLdFw
set
Table continues on next page
Section 11
1MRK 505 378-UEN A
Testing functionality by secondary injection
134
Line differential protection RED670 2.2 IEC
Commissioning manual
Summary of Contents for RED670 Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Page 2: ......
Page 18: ...12 ...
Page 36: ...30 ...
Page 68: ...62 ...
Page 72: ...66 ...
Page 108: ...102 ...
Page 278: ...272 ...
Page 282: ...276 ...
Page 288: ...282 ...
Page 306: ...300 ...
Page 307: ...301 ...