![ABB REC650 ANSI Technical Manual Download Page 86](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772086.webp)
IEC01000242_2_en.vsd
Activating
signal 2
LED 2
Manual
reset
Activating
signal 1
Automatic
reset
LED 1
Disturbance
tRestart
IEC01000242 V2 EN
Figure 25:
Operating sequence 6 (LatchedReset-S), manual reset
5.5.3
Function keys
5.5.3.1
Functionality
Local Human-Machine-Interface (LHMI) has five function buttons, directly to the left of
the LCD, that can be configured either as menu shortcut or control buttons. Each button
has an indication LED that can be configured in the application configuration.
When used as a menu shortcut, a function button provides a fast way to navigate between
default nodes in the menu tree. When used as a control, the button can control a binary
signal.
5.5.3.2
Operation principle
Each output on the FNKEYMD1 - FNKEYMD5 function blocks can be controlled from
the LHMI function keys. By pressing a function button on the LHMI, the output status of
the actual function block will change. These binary outputs can in turn be used to control
other function blocks, for example, switch control blocks, binary I/O outputs etc.
Section 5
1MRK 511 287-UUS A
Local Human-Machine-Interface LHMI
80