Name
Values (Range)
Unit
Step
Default
Description
OverTrigOp35
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 35
(on) or not (off)
OverTrigLe35
0 - 5000
%
1
200
Over trigger level for analog channel 35 in % of
signal
NomValue36
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 36
UnderTrigOp36
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 36
(on) or not (off)
UnderTrigLe36
0 - 200
%
1
50
Under trigger level for analog channel 36 in %
of signal
OverTrigOp36
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 36
(on) or not (off)
OverTrigLe36
0 - 5000
%
1
200
Over trigger level for analog channel 36 in % of
signal
NomValue37
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 37
UnderTrigOp37
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 37
(on) or not (off)
UnderTrigLe37
0 - 200
%
1
50
Under trigger level for analog channel 37 in %
of signal
OverTrigOp37
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 37
(on) or not (off)
OverTrigLe37
0 - 5000
%
1
200
Over trigger level for analog channel 37 in % of
signal
NomValue38
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 38
UnderTrigOp38
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 38
(on) or not (off)
UnderTrigLe38
0 - 200
%
1
50
Under trigger level for analog channel 38 in %
of signal
OverTrigOp38
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 38
(on) or not (off)
OverTrigLe38
0 - 5000
%
1
200
Over trigger level for analog channel 38 in % of
signal
NomValue39
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 39
UnderTrigOp39
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 39
(on) or not (off)
UnderTrigLe39
0 - 200
%
1
50
Under trigger level for analog channel 39 in %
of signal
OverTrigOp39
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 39
(on) or not (off)
OverTrigLe39
0 - 5000
%
1
200
Over trigger level for analog channel 39 in % of
signal
NomValue40
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 40
UnderTrigOp40
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 40
(on) or not (off)
Table continues on next page
Section 12
1MRK 511 287-UUS A
Monitoring
472
Technical manual