17.4
Binary inputs
Table 554:
Binary inputs
Description
Value
Operating range
Maximum input voltage 300 V DC
Rated voltage
24...250 V DC
Current drain
1.6...1.8 mA
Power consumption/input
<0.38 W
Threshold voltage
15...221 V DC (parametrizable in the range in steps of
1% of the rated voltage)
17.5
Signal outputs
Table 555:
Signal output and IRF output
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
10 A
Make and carry 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
≤0.5 A/≤0.1 A/≤0.04 A
17.6
Power outputs
Table 556:
Power output relays without TCM function
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
≤1 A/≤0.3 A/≤0.1 A