after a power interruption will return the state it had before or if it will be reset. For a Reset-
Set flip-flop, RESET input has higher priority over SET input.
Table 287:
Truth table for RSMEMORY function block
RESET
SET
OUT
NOUT
0
0
Last
value
Inverted last
value
0
1
0
1
1
0
1
0
1
1
0
1
Function block
RSMEMORY
SET
RESET
OUT
NOUT
IEC09000294-1-en.vsd
IEC09000294 V1 EN
Figure 177:
RSMEMORY function block
Signals
Table 288:
RSMEMORY Input signals
Name
Type
Default
Description
SET
BOOLEAN
0
Input signal to set
RESET
BOOLEAN
0
Input signal to reset
Table 289:
RSMEMORY Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
NOUT
BOOLEAN
Inverted output signal
Settings
Table 290:
RSMEMORY Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Memory
Disabled
Enabled
-
-
Enabled
Operating mode of the memory function