6.11.2.4
Settings
Table 93:
GOPPDOP (32) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disable / Enable
OpMode1
Disabled
OverPower
-
-
OverPower
Operation mode 1
Power1
0.0 - 500.0
%
0.1
1.0
Power setting for stage 1 in % of calculated
power base value
Angle1
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 1
TripDelay1
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 1
OpMode2
Disabled
OverPower
-
-
OverPower
Operation mode 2
Power2
0.0 - 500.0
%
0.1
1.0
Power setting for stage 2 in % of calculated
power base value
Angle2
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 2
TripDelay2
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 2
Table 94:
GOPPDOP (32) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
k
0.00 - 0.99
-
0.01
0.00
Low pass filter coefficient for power
measurement, V and I
Table 95:
GOPPDOP (32) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
-
-
Pos Seq
Mode of measurement for current and voltage
1MRK 511 287-UUS A
Section 6
Current protection
155
Technical manual