![ABB REC650 ANSI Technical Manual Download Page 473](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772473.webp)
Name
Values (Range)
Unit
Step
Default
Description
OverTrigOp04
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 4 (on)
or not (off)
OverTrigLe04
0 - 5000
%
1
200
Over trigger level for analog channel 4 in % of
signal
NomValue05
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 5
UnderTrigOp05
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 5
(on) or not (off)
UnderTrigLe05
0 - 200
%
1
50
Under trigger level for analog channel 5 in % of
signal
OverTrigOp05
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 5 (on)
or not (off)
OverTrigLe05
0 - 5000
%
1
200
Over trigger level for analog channel 5 in % of
signal
NomValue06
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 6
UnderTrigOp06
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 6
(on) or not (off)
UnderTrigLe06
0 - 200
%
1
50
Under trigger level for analog channel 6 in % of
signal
OverTrigOp06
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 6 (on)
or not (off)
OverTrigLe06
0 - 5000
%
1
200
Over trigger level for analog channel 6 in % of
signal
NomValue07
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 7
UnderTrigOp07
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 7
(on) or not (off)
UnderTrigLe07
0 - 200
%
1
50
Under trigger level for analog channel 7 in % of
signal
OverTrigOp07
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 7 (on)
or not (off)
OverTrigLe07
0 - 5000
%
1
200
Over trigger level for analog channel 7 in % of
signal
NomValue08
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 8
UnderTrigOp08
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 8
(on) or not (off)
UnderTrigLe08
0 - 200
%
1
50
Under trigger level for analog channel 8 in % of
signal
OverTrigOp08
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 8 (on)
or not (off)
OverTrigLe08
0 - 5000
%
1
200
Over trigger level for analog channel 8 in % of
signal
NomValue09
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 9
UnderTrigOp09
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 9
(on) or not (off)
Table continues on next page
1MRK 511 287-UUS A
Section 12