10.3.2.4
Signals
Table 176:
SCSWI Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
PSTO
INTEGER
2
Operator place selection
L_SEL
BOOLEAN
0
Select signal from local panel
L_OPEN
BOOLEAN
0
Open signal from local panel
L_CLOSE
BOOLEAN
0
Close signal from local panel
AU_OPEN
BOOLEAN
0
Used for local automation function
AU_CLOSE
BOOLEAN
0
Used for local automation function
BL_CMD
BOOLEAN
0
Steady signal for block of the command
RES_EXT
BOOLEAN
0
Reservation is made externally
SY_INPRO
BOOLEAN
0
Synchronizing function in progress
SYNC_OK
BOOLEAN
0
Closing is permitted by the synchronism-check
EN_OPEN
BOOLEAN
0
Enables open operation
EN_CLOSE
BOOLEAN
0
Enables close operation
XPOS
GROUP
SIGNAL
-
Group signal from XCBR/XSWI
Table 177:
SCSWI Output signals
Name
Type
Description
EXE_OP
BOOLEAN
Execute Open command
EXE_CL
BOOLEAN
Execute Close command
SELECTED
BOOLEAN
Select conditions are fulfilled
START_SY
BOOLEAN
Starts the synchronizing function
POSITION
INTEGER
Position indication
OPENPOS
BOOLEAN
Open position indication
CLOSEPOS
BOOLEAN
Closed position indication
CMD_BLK
BOOLEAN
Commands are blocked
L_CAUSE
INTEGER
Latest value of the error indication during command
POS_INTR
BOOLEAN
Stopped in intermediate position
XOUT
BOOLEAN
Execution information to XCBR/XSWI
Section 10
1MRK 511 287-UUS A
Control
250
Technical manual