10.3.2.5
Settings
Table 178:
SCSWI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CtlModel
Dir Norm
SBO Enh
-
-
SBO Enh
Specifies control model type
PosDependent
Always permitted
Not perm at 00/11
-
-
Always permitted
Permission to operate depending on the
position
tSelect
0.000 - 60.000
s
0.001
30.000
Maximum time between select and execute
signals
tSynchrocheck
0.00 - 600.00
s
0.01
10.00
Allowed time for synchronism-check to fulfil
close conditions
tSynchronizing
0.00 - 600.00
s
0.01
0.00
Supervision time to get the signal
synchronizing in progress
tExecutionFB
0.00 - 600.00
s
0.01
30.00
Maximum time from command execution to
termination
10.3.3
Circuit breaker SXCBR
10.3.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Circuit breaker
SXCBR
-
-
10.3.3.2
Functionality
The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions and
to perform the control operations, that is, pass all the commands to primary apparatuses in
the form of circuit breakers via binary output boards and to supervise the switching
operation and position.
1MRK 511 287-UUS A
Section 10
Control
251
Technical manual