Name
Type
Description
VB_RANGE
INTEGER
V_B Amplitude range
VB_ANGL
REAL
V_B Angle, magnitude of reported value
V_C
REAL
V_C Amplitude, magnitude of reported value
VC_RANGE
INTEGER
V_C Amplitude range
VC_ANGL
REAL
VC Angle, magnitude of reported value
12.1.7.4
Settings
Table 364:
VNMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disbled/Enabled operation
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
VDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
VMax
0 - 2000000
V
1
106000
Maximum value
VRepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
VLimHys
0.000 - 100.000
V
0.001
5.000
Hysteresis value in % of range and is common
for all limits
VAngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Table 365:
VNMMXU Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
VZeroDb
0 - 100000
m%
1
500
Zero point clamping in 0.001% of range
VHiHiLim
0 - 2000000
V
1
96000
High High limit (physical value)
VHiLim
0 - 2000000
V
1
86000
High limit (physical value)
VLowLim
0 - 2000000
V
1
71000
Low limit (physical value)
VLowLowLim
0 - 2000000
V
1
66000
Low Low limit (physical value)
VMin
0 - 2000000
V
1
0
Minimum value
Section 12
1MRK 511 287-UUS A
Monitoring
438
Technical manual