Name
Values (Range)
Unit
Step
Default
Description
3I2PU
1 - 100
%IB
1
10
Pickup of negative sequence undercurrent
element in % of IBase
OpDVDI
Disabled
Enabled
-
-
Disabled
Operation of change based function Disable/
Enable
DVPU
1 - 100
%VB
1
60
Pickup of change in phase voltage in % of
VBase
DIPU
1 - 100
%IB
1
15
Pickup of change in phase current in % of
IBase
VPPU
1 - 100
%VB
1
70
Pickup of phase voltage in % of VBase
50P
1 - 100
%IB
1
10
Pickup of phase current in % of IBase
SealIn
Disabled
Enabled
-
-
Enabled
Seal in functionality Disable/Enable
VSealInPU
1 - 100
%VB
1
70
Pickup of seal-in phase voltage in % of VBase
IDLDPU
1 - 100
%IB
1
5
Pickup for phase current detection in % of
IBase for dead line detection
VDLDPU
1 - 100
%VB
1
60
Pickup for phase voltage detection in % of
VBase for dead line detection
Table 158:
SDDRFUF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
9.2.6
Monitored data
Table 159:
SDDRFUF Monitored data
Name
Type
Values (Range)
Unit
Description
3I0
REAL
-
A
Magnitude of zero sequence
current
3I2
REAL
-
A
Magnitude of negative
sequence current
3V0
REAL
-
kV
Magnitude of zero sequence
voltage
3V2
REAL
-
kV
Magnitude of negative
sequence voltage
1MRK 511 287-UUS A
Section 9
Secondary system supervision
209
Technical manual