Settings
Table 297:
PULSETIMERQT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
t
0.000 - 90000.000
s
0.001
0.010
Pulse time length
11.3.2.5
XORQT function block
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
XORQT function block
XORQT
-
-
Functionality
The exclusive OR function (XORQT) function is used to generate combinatory
expressions with boolean variables. XORQT function has two inputs and two outputs.
One of the outputs is inverted. The output signal is 1 if the input signals are different and
0 if they are equal.
Function block
XORQT
INPUT1
INPUT2
OUT
NOUT
IEC09000300-1-en.vsd
IEC09000300 V1 EN
Figure 181:
XORQT function block
Signals
Table 298:
XORQT Input signals
Name
Type
Default
Description
INPUT1
BOOLEAN
0
Input signal 1
INPUT2
BOOLEAN
0
Input signal 2
Table 299:
XORQT Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
NOUT
BOOLEAN
Inverted output signal
Section 11
1MRK 511 287-UUS A
Logic
388
Technical manual