![background image](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772486.webp)
Name
Values (Range)
Unit
Step
Default
Description
IndicationMa15
Hide
Show
-
-
Hide
Indication mask for binary channel 15
TrigLevel16
Trig on 0
Trig on 1
-
-
Trig on 1
Trigger on positive (1) or negative (0) slope for
binary input 16
IndicationMa16
Hide
Show
-
-
Hide
Indication mask for binary channel 16
12.4.6
Operation principle
Disturbance report DRPRDRE is a common name for several functions to supply the
operator, analysis engineer, and so on, with sufficient information about events in the
system.
The functions included in the disturbance report are:
•
Sequential of events
•
Indications
•
Event recorder
•
Trip value recorder
•
Disturbance recorder
shows the relations between Disturbance Report, included functions and
function blocks. Sequential of events , Event recorder and Indications uses information
from the binary input function blocks (BxRBDR). Trip value recorder uses analog
information from the analog input function blocks (AxRADR). Disturbance recorder
DRPRDRE acquires information from both AxRADR and BxRBDR.
Section 12
1MRK 511 287-UUS A
Monitoring
480
Technical manual
Summary of Contents for REC650 ANSI