15.2
Time synchronization
15.2.1
Functionality
The time synchronization source selector is used to select a common source of absolute
time for the IED when it is a part of a control and a protection system. This makes it
possible to compare event and disturbance data between all IEDs in a station automation
system.
Micro SCADA OPC server should not be used as a time synchronization
source.
15.2.2
Time synchronization TIMESYNCHGEN
15.2.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization
TIMESYNCHGE
N
-
-
15.2.2.2
Settings
Table 491:
TIMESYNCHGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CoarseSyncSrc
Disabled
SNTP
DNP
IEC60870-5-103
-
-
Disabled
Coarse time synchronization source
FineSyncSource
Disabled
SNTP
IRIG-B
-
-
Disabled
Fine time synchronization source
SyncMaster
Disabled
SNTP-Server
-
-
Disabled
Activate IED as synchronization master
Section 15
1MRK 511 287-UUS A
Basic IED functions
590
Technical manual