Name
Type
Description
UPD_BLKD
BOOLEAN
Update of position indication is blocked
POSITION
INTEGER
Apparatus position indication
OPENPOS
BOOLEAN
Apparatus open position
CLOSEPOS
BOOLEAN
Apparatus closed position
TR_POS
INTEGER
Truck position indication
CNT_VAL
INTEGER
Operation counter value
L_CAUSE
INTEGER
Latest value of the error indication during command
10.3.3.5
Settings
Table 181:
SXCBR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
tStartMove
0.000 - 60.000
s
0.001
0.100
Supervision time for the apparatus to move
after a command
tIntermediate
0.000 - 60.000
s
0.001
0.150
Allowed time for intermediate position
AdaptivePulse
Not adaptive
Adaptive
-
-
Not adaptive
Output resets when a new correct end position
is reached
tOpenPulse
0.000 - 60.000
s
0.001
0.200
Output pulse length for open command
tClosePulse
0.000 - 60.000
s
0.001
0.200
Output pulse length for close command
SuppressMidPos
Disabled
Enabled
-
-
Enabled
Mid-position is suppressed during the time
tIntermediate
10.3.4
Circuit switch SXSWI
10.3.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Circuit switch
SXSWI
-
-
10.3.4.2
Functionality
The purpose of Circuit switch (SXSWI) function is to provide the actual status of positions
and to perform the control operations, that is, pass all the commands to primary
apparatuses in the form of disconnectors or grounding switches via binary output boards
and to supervise the switching operation and position.
1MRK 511 287-UUS A
Section 10
Control
253
Technical manual