Technical data
Table 170:
SESRSYN (25) technical data
Function
Range or value
Accuracy
Phase shift,
j
line
-
j
bus
(-180 to 180) degrees
-
Voltage ratio, V
bus
/V
line
0.500 - 2.000
-
Reset ratio, synchronism check
> 95%
-
Frequency difference limit
between bus and line for
synchrocheck
(0.003-1.000) Hz
± 2.0 mHz
Phase angle difference limit
between bus and line for
synchrocheck
(5.0-90.0) degrees
± 2.0 degrees
Voltage difference limit between
bus and line for synchronizing and
synchrocheck
0.03-0.50 p.u
± 0.5% of V
n
Time delay output for synchronism
check
(0.000-60.000) s
± 0.5% ± 25 ms
Frequency difference minimum
limit for synchronizing
(0.003-0.250) Hz
± 2.0 mHz
Frequency difference maximum
limit for synchronizing
(0.050-0.500) Hz
± 2.0 mHz
Maximum allowed frequency rate
of change
(0.000-0.500) Hz/s
± 10.0 mHz/s
Closing time of the breaker
(0.000-60.000) s
± 0.5% ± 25 ms
Breaker closing pulse duration
(0.050-60.000) s
± 0.5% ± 25 ms
tMaxSynch, which resets
synchronizing function if no close
has been made before set time
(0.000-60.000) s
± 0.5% ± 25 ms
Minimum time to accept
synchronizing conditions
(0.000-60.000) s
± 0.5% ± 25 ms
Time delay output for energizing
check
(0.000-60.000) s
± 0.5% ± 25 ms
Operate time for synchronism
check function
40 ms typically
-
Operate time for energizing
function
100 ms typically
-
10.2
Autorecloser for 3-phase operation SMBRREC (79)
1MRK 511 287-UUS A
Section 10
Control
237
Technical manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 60: ...54 ...
Page 66: ...60 ...
Page 424: ...418 ...
Page 566: ...560 ...
Page 636: ...630 ...
Page 699: ...693 ...