Minimize the number of recordings:
•
Binary signals: Use only relevant signals to start the recording that is, protection trip,
carrier receive and/or start signals.
•
Analog signals: The level triggering should be used with great care, since unfortunate
settings will cause enormously number of recordings. If nevertheless analog input
triggering is used, chose settings by a sufficient margin from normal operation values.
Phase voltages are not recommended for trigging.
There is a risk of flash wear out if the disturbance report triggers too often.
Remember that values of parameters set elsewhere are linked to the information on a report.
Such parameters are, for example, station and object identifiers, CT and VT ratios.
14.7
Logical signal status report BINSTATREP
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
14.7.1
Identification
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logical signal status report
BINSTATREP
-
-
14.7.2
Application
GUID-F9D225B1-68F7-4D15-AA89-C9211B450D19 v3
The Logical signal status report (BINSTATREP) function makes it possible to poll signals from
various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs and can be
read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.
t
t
INPUTn
OUTPUTn
IEC09000732-1-en.vsd
IEC09000732 V1 EN-US
Figure 201: BINSTATREP logical diagram
14.7.3
Setting guidelines
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
The pulse time
t is the only setting for the Logical signal status report (BINSTATREP). Each
output can be set or reset individually, but the pulse time will be the same for all outputs in the
entire BINSTATREP function.
Section 14
1MRK 505 370-UEN D
Monitoring
376
Busbar protection REB670
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...