Section 4
Analog inputs
4.1
Introduction
SEMOD55003-5 v11
Analog input channels must be configured and set properly in order to get correct
measurement results and correct protection operations. For power measuring, all directional
and differential functions, the directions of the input currents must be defined in order to
reflect the way the current transformers are installed/connected in the field ( primary and
secondary connections ). Measuring and protection algorithms in the IED use primary system
quantities. Setting values are in primary quantities as well and it is important to set the data
about the connected current and voltage transformers properly.
An AISVBAS reference
PhaseAngleRef can be defined to facilitate service values reading. This
analog channel's phase angle will always be fixed to zero degrees and remaining analog
channel's phase angle information will be shown in relation to this analog input. During testing
and commissioning of the IED, the reference channel can be changed to facilitate testing and
service values reading.
The IED has the ability to receive analog values from primary equipment, that
are sampled by Merging units (MU) connected to a process bus, via the IEC
61850-9-2 LE protocol.
The availability of VT inputs depends on the ordered transformer input module
(TRM) type.
4.2
Setting guidelines
SEMOD55068-1 v1
SEMOD130348-4 v5
The available setting parameters related to analog inputs are depending on the
actual hardware (TRM) and the logic configuration made in PCM600.
If a second TRM is used, at least one TRM channel must be configured to get
the service values. However, the MU physical channel must be configured to get
service values from that channel.
4.2.1
Setting of the phase reference channel
SEMOD55055-5 v3
All phase angles are calculated in relation to a defined reference. An appropriate analog input
channel is selected and used as phase reference. The parameter
PhaseAngleRef defines the
analog channel that is used as phase angle reference.
1MRK 505 370-UEN D
Section 4
Analog inputs
Busbar protection REB670
59
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...